Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03850 7/18/06

1. Panels A and PP are fully rated 22K on their panel schedules. This appears to be inconsistent with the Series Rated Notes on Sheet E3.
2. Plot the location of Panel A and the service on the plans, and provide fault calculations for AFC at all new panels.
3. Equipment Grounding Conductors in the conduit between the gutter and the disconnects, both new and existing, shall be sized according to Table 250.122. Minimum 1/0 for the line side 800AF.
4. The ampacity of the tap conductors in the conduit between the gutter and disconnects shall be a minimum of #4 to meet the requirements of NEC 240.21 (B) (1) (4).
07/24/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
08/04/2006 JMORALE1 ENGINEERING REVIEW Needs Review
08/04/2006 JMORALE1 WWM REVIEW Needs Review
08/04/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/04/2006 JMORALE1 ZONING REVIEW Needs Review