Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03850
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM03850 7/18/06 1. Panels A and PP are fully rated 22K on their panel schedules. This appears to be inconsistent with the Series Rated Notes on Sheet E3. 2. Plot the location of Panel A and the service on the plans, and provide fault calculations for AFC at all new panels. 3. Equipment Grounding Conductors in the conduit between the gutter and the disconnects, both new and existing, shall be sized according to Table 250.122. Minimum 1/0 for the line side 800AF. 4. The ampacity of the tap conductors in the conduit between the gutter and disconnects shall be a minimum of #4 to meet the requirements of NEC 240.21 (B) (1) (4). |