Permit Number: T06CM03850
Parcel: 117021150

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03850
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2006 DAVE MANN FIRE REVIEW Approved
06/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/30/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03850 6/30/06

1. Please eliminate the GNDs on the line side of the service disconnect. Reference NEC 250.24 (B), 250.28, 250.142 (A) (1).
2. Since this service is being converted from a 240V to a 208V, please verify and document on the plans that there are no 240V loads which can not be fed by 208V power.
3. Verify that each of the 6 existing disconnect switches either already are associated with the 65/10 series rating, or will be retrofitted into that rating. Be very clear in this regard on a case-by-case basis.
06/30/2006 ROBERT SHERRY WATER REVIEW Approved
06/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/18/2006 AOLIVO1 WWM REVIEW Needs Review
07/18/2006 AOLIVO1 BUILDING-COMMERCIAL REVIEW Needs Review
07/18/2006 AOLIVO1 ENGINEERING REVIEW Needs Review
07/18/2006 AOLIVO1 ZONING REVIEW Needs Review
07/18/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review