Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03850
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/30/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM03850 6/30/06 1. Please eliminate the GNDs on the line side of the service disconnect. Reference NEC 250.24 (B), 250.28, 250.142 (A) (1). 2. Since this service is being converted from a 240V to a 208V, please verify and document on the plans that there are no 240V loads which can not be fed by 208V power. 3. Verify that each of the 6 existing disconnect switches either already are associated with the 65/10 series rating, or will be retrofitted into that rating. Be very clear in this regard on a case-by-case basis. |
| 06/30/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/30/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/18/2006 | AOLIVO1 | WWM | REVIEW | Needs Review | |
| 07/18/2006 | AOLIVO1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/18/2006 | AOLIVO1 | ENGINEERING | REVIEW | Needs Review | |
| 07/18/2006 | AOLIVO1 | ZONING | REVIEW | Needs Review | |
| 07/18/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |