Permit Number: T06CM03838
Parcel: 131020500

Address:
5402 E 27TH ST

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM03838
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1) Provide the size of the overcurrent protective device the photovoltaic system feeds at the existing service disconnect.

2) Provide the exact wording for the marking required by 690.53.

3) Provide the exact wording for the warning sign required by 690.17.
07/20/2006 DAVE WITT BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/20/2006 CINDY AGUILAR OUT TO CUSTOMER Completed