Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06CM03836
Parcel: 141015530

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM03836
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2006 WILDAN 2ND PARTY REVIEW REVIEW Denied September 7, 2006



Development Services Department
City of Tucson
P.O. Box 27210
Tucson, AZ 85726

RE: CABRANES RESIDENCE – 2nd Review
CITY OF TUCSON LOG NO. T04CM003836
WILLDAN PROJECT NO. 13881-6033

The initial review for the above project has been completed. This letter reflects comments which need to be addressed by a written response to each, indicating action taken. In order to facilitate a shorter back-check time, we request that you please provide two (2) sets revised plans and calculations, highlighting any changes with appropriate revision number, revision date, and “cloud bubbles.” Please replace all revised drawing sheets, in all sets of plans, before returning to Willdan for the follow-up plan review. Please return redline drawings with your resubmittal.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 1994 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.


Occupancy
Occup. Load
Construction
Area S.F.
Sprinklered
Alarms
SFR
Garage
Patio N/A V-B 2545
592
70 No Smoke

Special Inspection is required for the following items:

Post-tensioned slab

GENERAL COMMENTS:
A signed special inspection form from the City of Tucson is required at the time that the plans are resubmitted for a back check. Reference the City of Tucson Submittal Policy.

ARCHITECTURAL COMMENTS:
Sheet A2.0
For thin-coat stucco systems over foam board, note and specify the listing agency’s evaluation report number, system name and manufacturer, and note and specify the vapor barrier. Reference the City of Tucson Submittal Requirements. COMMENT REMAINS: Please provide evaluation report number.

Sheet A4.0
Show calculation of attic ventilation area. Note location of all vents needed to comply or show compliance with an accepted Non-vented Roof Method Details 1-8, Dated 7/18-19/2001 as permitted by Section R104.11, Alternate Methods. Reference IRC Section R806.2. COMMENT REMAINS: Please provide compliance to the unvented methods and requirements.

STRUCTURAL COMMENTS:
Sheet S1
Indicate the slope for exterior slabs. Reference IRC Section R311.6.1. COMMENT REMAINS: Indicate for front covered porch.

PLUMBING COMMENTS:
Reviewed and accepted.

MECHANICAL COMMENTS:
Sheet M1.0
Show on the plans how mechanical fresh air will be provided if using one of the non-vented roof methods. Reference Non-Vented Roof Details Dated 7/18-19/2001. COMMENT REMAINS: Not addressed.

ELECTRICAL COMMENTS:
Sheet E2.0
Please provide cut sheets for all the exterior light fixtures shown or noted on Model plans. The cut sheets need to provide lumens per fixture and show if the fixture is a full cut-off, which means no light is emitted at or above the horizontal plane. For non-Model plans, please provide cut sheets and calculations for all exterior lighting fixtures. Reference the City of Tucson Outdoor Lighting Code. COMMENT REMAINS: There are three options. Please specify which option will be used.

Cross-reference exterior lighting fixtures on the plans with the cut sheets and calculations submitted. Reference the City of Tucson Submittal Requirements. COMMENT REMAINS: FCO lumens are over the limit by 1610, if using a 1200 lumen bulb with the medium fixture.

Sheet E3.0
Note on plans: “All branch circuits that supply 125-volt, single-phase, 15- and 20-ampere outlets installed in dwelling unit bedrooms shall be protected by an arc fault circuit interrupter listed to provide protection for the entire branch circuit.” Reference IRC Section E3802.11. COMMENT REMAINS: Not addressed.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
09/13/2006 GERARDO BONILLA REJECT SHELF Completed