Permit Number: T06CM03798
Parcel: 140410530

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM03798
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2007 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed $75,237.50 in West DIstrict. 125 rooms
01/05/2007 HEATHER THRALL ZONING REVIEW Denied Zoning will be able to review the building plans over the counter once the site plan is approved by all divisions of DSD.
12/18/2006 ROBERT SHERRY WATER REVIEW Approved
12/20/2006 DAVE MANN FIRE REVIEW Denied Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.
12/28/2006 GERRY KOZIOL WWM REVIEW Denied needs to show location/method of connection to public sewer
12/29/2006 JASON GREEN ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2007 SUE REEVES REJECT SHELF Completed
01/23/2007 SUE REEVES OUT TO CUSTOMER Completed