Permit Number: T06CM03798
Parcel: 140410530

Review Status: Completed

Review Details: SITE

Permit Number - T06CM03798
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2006 MARTIN BROWN FIRE REVIEW Approved
07/13/2006 JOE LINVILLE NPPO REVIEW Denied See comments under Landscape.
07/13/2006 JOE LINVILLE LANDSCAPE REVIEW Denied 1) All lettering and dimensions shall be the equivalent of twelve (0.12") point or greater in size. Revise the landscape plans and NPP plans as necessary DS 2-05.2.1.A.

2) Revise the landscape plan to include slope ratios for retention and detention basins. Basin slopes in most instances are required to have slopes no steeper than 4:1 where depths are three feet and greater, 3:1 for unprotected slopes and 2: 1 for protected slopes for depths less than three feet. Revise the site plan as necessary. DS 10-01.4

3) Revise note ten on sheet 1 of the landscape plan to indicate 50 percent.

4) Regarding berms shown on the landscape plan along Country Club Road: Per DS 2-06.3.7.B.5.d "the highest point of the berms must be on site and no closer than one (1) foot from the property line or the MS&R right-of-way line, whichever is more strict. The one (1) foot distance from the property line on the location of the berm crest is a minimum. In most cases, it will be greater than one (1) foot unless there is excess right-of-way, and the City Engineer's Office allows the berm to occur within the right-of-way area".
Revise the plan as necessary. Obtain approval, in writing for the concept of construction berms in the right-of-way and forward with resubmittal.

5) Sheet 2 of the site plan at Basin 'B' includes the notation "Engineered floor throughout". Clarify if there is an associated detail and the extent of its application.

6) Revise notes on sheet 2 & 3 of the landscape plan that refer to a sheet 8, no sheet 8 was included.

7) Screens are allowed by Code to encroach only three feet into the minimum width required for the street landscape border. Revise the Valencia Road segment where necessary. DS 2-06.3.7.B.5

8) In situations where the street landscape border is wider than the minimum ten (10) foot requirement, the landscape border width needs to be determined for the purposes of calculating the fifty (50) percent vegetative coverage requirement, Sec. 3.7.2.4 of the LUC. The width is that area between the required screen and the property line. Revise the calculations and plan elements where necessary for Country Club Road. DS 2-06.3.4.C.2

9) The area between the right-of-way line and sidewalk and the area between the sidewalk and the curb, if not covered with vegetation, shall be covered with an appropriate inorganic ground cover, such as decomposed granite. Revise the plans to clarify compliance. LUC 3.7.2.4.A.4

10) Trees and shrubs are to be selected and located so that, at maturity, they do not interfere with existing on-site or off-site utility service lines or utility easements or with solar access. Obtain clearances and revise the plans as necessary. LUC 3.7.2.6.B

11) All plant material used for landscaping shall be selected from the Drought Tolerant Plant List in Development Standard 2-16.0. except those used in oasis areas. Platanus wrightii is not on the approved list and the planting areas selected do not conform to DS 2-06.3.2.B, LUC 3.7.2.2.C.

12) Identify screening proposed the refuse storage and mechanical equipment areas on the landscape and site plans. LUC Table 3.7.2-I

13) A landscape border is required at all points along Bonney Avenue except for approved ingress/egress locations. Refuse containers are to be placed so that the collection vehicle does not have to back into moving traffic, on or off the premises. DS 6-01.4.1.I

14) Revise the note titled "Fencing" on sheet 1 of the native plant preservation plan to reference the Development Services Department Landscape Section, rather than Parks and Recreation.

15) Revise the native plant preservation plan to meet the minimum preservation requirements of LUC 3.8.6.2.A. Correct the landscape plans as necessary.

16) Revise the native plant preservation plan to meet the minimum mitigation requirements of LUC Table 3.8.6-I. Correct the landscape plans as necessary.
08/29/2006 HEATHER THRALL ZONING REVIEW Denied TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: T06CM03798
6575 S. Country Club Road, New Hilton Garden Inn
Commercial Site Plan

TRANSMITTAL DATE: September 8, 2006

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This plan was reviewed for compliance with the Land Use Code (LUC), Development Standard (DS), American National Standard Institute (ANSI) and International Building Code 2003 (IBC), and content requirements of DS 2-02.

2. Per DS 2-02.2.1.2, please revise the property description in title block to read Township 15, Range 14, Section 16.

3. Per DS 2-02.2.1.3, please provide the site address (6575 S. Country Club per Assessor)

4. Per DS 2-02.2.1.4, on location map, please revise caption to read Range 14 East.

5. Per DS 2-02.2.1.6, with regards to buildings information:
A) please clarify in general note that the 39' height for the hotel is the maximum allowed height per Annexation Case C15-88-01, ordinance 7090. In addition, please provide a note that height is measured from design grade to top of roof for parapet design, or mid-point of pitch for gable roof design.

Please provide height for the pool house and the cabana.

6. Per DS 2-02.2.1.7, Staff acknowledges the building setbacks meet code. For records, please provide all building setbacks. Along Valencia and Country Club, please label future curb locations (existing curb if maximum right of way taken) and give building setbacks from these curb locations. Along Bonney Ave, give setback from property line at closest point to building, and give distance from property line to future curb proposed.

7. Per DS 2-02.2.1.8, with regards to handicapped parking:
A) increase post height for general handicapped sign to 7' from grade to bottom of sign (not including van accessible sign)
B) add truncated domes (early detectable warnings per ANSI 705.5) to all handicapped ramps where transitioning from pedestrian to vehicular use area
C) please correct detail drawing 4 on sheet 3 to show the wheel stop barrier fully contained within 2'6" of the top of the parking space (Per DS 3-05)

8. Per DS 2-02.2.1.9, with regards to bicycle parking: (DS 2-09 has been updated on web)
A) Per DS 2-09.4.1, class 2 bicycle parking facilities will be located no more than 50 feet from main building entrances and will be along the front of the building as well as along other sides of the building that have entrances. Please relocate the bicycle parking to meet this criteria, and advise where all building entrances are planned.
B) Please provide bicycle parking detail drawings to ensure DS 2-09 is met.

9. Per DS 2-02.2.1.11, please provide dimensions for all PAAL widths/entries/exits.

10. Per DS 2-02.2.1.12 and DS 2-08, with regards to pedestrian/accessible routes:
A) a continuous pedestrian/accessible route is needed from all streets this project is bounded by (Valencia, Country Club, Bonney) to the building.
B) please label widths of all sidewalks and crosswalks
C) ensure handicapped ramps are provided where applicable.
D) ensure all handicapped ramps have truncated domes per ANSI 705.5.

11. Per DS 2-02.2.1.13, please provide details for any free-standing signage.

12. Per DS 2-02.2.1.14/LUC 3.4.5.5, a minimum of two loading zones (12x35) are required, as the project is over 50,000 GFA. The one loading zone provided meets code.

13. Per DS 2-02.2.1.20, please just check to ensure all easements are shown on the plan.

14. As the property is comprised of more than one lot, a lot combination and associated lot combination covenants should be recorded. These forms are available at our website, www.tucsonaz.gov/dsd under forms. Please provide copies & recordation receipts.

15. Per DS 2-02.2.1.25, Please provide details for free-standing lighting (base width, height) and ensure lighting does not affect vehicle or pedestrian clearances.

16. Per DS 2-02.2.2.A, give gross and net lot area, and lot area per zone.

17. Per DS 2-02.2.2.A.2, give gross floor area ratio for each zone & clarify in FAR & square footage notes what accessory structures are included (pool house AND cabana?)

18. With regards to general notes:
A) Please revise general note 25 to read "minimum building setback required is: the greater of 21' or the height of the exterior building wall from back of future curb for Valencia and Country Club frontage".
B) Please remove the notation of county case C012-83-44 from the plan.
C) Please correct the general note 2 to read that the property is "zoned C-2 and I-1 with annexation restrictions".

19. Please note, further review comments may be forthcoming, depending upon the responses provided. Should you have any questions, please contact me at Heather.Thrall@tucsonaz.gov or at 791-4541x1156.

If you have any questions about this transmittal, please call (520) 791-5608.

HCT C:\planning\site\DSD\T06CM03798 6575 s country club hilton.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
09/08/2006 HEATHER THRALL ZONING HC SITE REVIEW Denied Please see zoning review comments.
09/11/2006 JASON GREEN ENGINEERING REVIEW Denied DATE: September 19, 2006
SUBJECT: 6575 S Country Club Road- Engineering Review of site plan and grading plan
TO: Metro Permits Express
LOCATION: T15S R14E Sec16, Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: T06CM03798 (site plan) and T06BU01659 (grading plan)


SUMMARY: Engineering Division of Development Services Department has received and reviewed the site plan (T06CM03798), grading permit application (T06BU01659), and drainage report (prepared by The WLB Group, Inc.) for the above referenced property. Engineering Division does not recommend approval of the site plan or grading permit application at this time. The drainage report was reviewed for site plan and grading plan purposes only. The following items need to be addressed:


SITE PLAN COMMENTS:

1) Provide a copy of the approved Improvement Plans referenced for the reconstruction of the existing cul-de-sac located at S Bonney Ave. The proposed site plan and grading plan must be in conformance with any proposed C.O.T. Improvement Plans. Or provide acceptance by Tucson Department of Transportation (Traffic Division).

2) DS Sec.2-02.2.1.A.2: Revise the property description in title block to read Township 15, Range 14, Section 16.

3) DS Sec.2-02.2.1.A.3: Provide the site address for the subject parcel on Sheet 1 of 4.

4) DS Sec.2-02.2.1.A.4: Revise the location map on Sheet 1 of 4 to read Range 14. Provide conditions within the square mile area shown on the project location map located on Sheet 1, such as subdivisions. Reference recorded subdivision plats by book and page numbers.

5) DS Sec.2-02.2.1.A.10: Show existing and future sight visibility triangles (SVT) on plan view for all PAAL access points. Revise the SVT shown for Country Club Road to reflect the dimensions for an Arterial Street. Refer to DS Sec3-01.5.1 for sight visibility triangle procedures and criteria. Parking spaces, signs, landscape and walls will not be approved within the future right-of-way.

6) DS Sec.2-02.2.1.A.11: Depict and label the 25-feet radii concrete curbs per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213) at all of the driveway entrances located on Valencia Road and Country Club Road. The curbs should be constructed at the edge of pavement, which must also be depicted on the site plan. Curb returns must be constructed entirely within the subject parcel refer to DS Sec.3-01.3.2.C for street development standards.

7) DS Sec.2-02.2.1.A.12: Provide a continuous pedestrian circulation path that connects all public access areas of the proposed building and the proposed circulation path located on Valencia Road, Country Club Road and Bonney Avenue. Truncated domes are required for all proposed handicap access ramps.

8) DS Sec.2-02.2.1.A.14: Provide the required maneuvering area for all loading zones that are shown on the development plan. Refer to AASHTO for the national standards for turning radii.

9) DS Sec.2-02.2.1.A.15: Provide the 100-year floodplain limits with the calculated water surface elevations for the proposed channel and the 100-year ponding limits for the proposed 14-EF-1 grate inlets and modified trench drain in the cul-de-sac of Bonney Ave.

10) DS Sec.2-02.2.1.A.16: Provide a detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalk. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk.

11) DS Sec.2-02.2.1.A.19: Provide the dimensioned MS&R right-of-way width for both Valencia Road and Country Club Road. Label future curb and sidewalk locations (existing curb and sidewalk if maximum right of way taken)

12) DS Sec.3-01.3.3.A: Provide on the site plan the required 6-foot wide sidewalk with curb along the street frontage of Country Club Road. Per the adopted Mayor and Counsel policy all sidewalks along MS&R right-of-ways for arterial and collector streets require 6-foot wide sidewalks. Label the sidewalk to be constructed as 6-foot.

13) DS Sec.2-02.2.1.A.20: Provide the Docket and Page number for the 25'Right-of-way that is shown for Valencia Road in the upper left corner of Sheet2 of 4.

14) DS Sec.2-02.2.1.A.27: Revise Site Note #3 to call out wall dimensions and as to whether it is existing or is to be constructed.

15) DS Sec.2-02.2.1.A.32: Provide a detail showing the dimensions for refuse container, the enclosure must have a minimum inside clear dimension of 10 feet by 10 feet between steel pipes that are required between the container and the enclosure's rear and sidewall. Refer to DS Sec.6-01.4.2 for specifications and requirements on access, placement of containers, bin enclosure and construction. Show maneuverability for refuse vehicles in plan view.


GRADING PLAN COMMENTS:

16) DS Sec.11-01.4.1.C: Revise the title of the plan sheet submitted to read Site and Grading Plan for Hilton Garden Inn, or provide separate plan sheets with all of the grading plan information that is required to meet the standards outlined in DS Sec.11-01.

17) DS Sec.11-01.4.1.C.3: Provide spot elevation within the cul-de-sac and around the proposed 14 EF-1 grate inlets showing proposed finished contours to be achieved by grading.

18) DS Sec.11-01.4.1.C.4: Provide a detail or Improvement Standard reference for the proposed 14 EF-1 grate inlets and show how storm water is conveyed to the proposed channel. Provide a detail for the 7'x3' wide modified trench drains that are called out in the cul-de-sac.

19) DS Sec.11-01: Provide general grading notes, including a grading/drainage note specifying conformance with City of Tucson Development Standard 11-01.0 (excavation and grading requirements).

20) DS 10-02.0, Section 14.3.2: Revise General Note #28 on the site plan to accurately read the following from the Development Standards, (a) the owner or owners shall be solely responsible for operation, maintenance, and liability for drainage structures and detention basins; (b) that the owner or owners shall have an Arizona Registered Professional Civil Engineer prepare a certified inspection report for the drainage and detention/retention facilities at lease once each year, and that these regular inspection reports will be on file with the owner for review by City staff, upon written request; (c) that City staff may periodically inspect the drainage and retention/detention facilities to verify that scheduled and unscheduled maintenance activities are being performed adequately; and (d) that the owner or owners agree to reimburse the City for any and all costs associated with the maintaining of the drainage and detention/retention facilities, should the City find the owner or owners deficient in their obligation to adequately operate and maintain their facilities".

21) DS Sec.11-01.4.1.C.4: Provide a General Note stating that all retaining walls will require a separate permit for review and approval by all necessary Development Services Departments.

22) DS Sec.11-01.4.1.C.4: Revise Detail #1 on Sheet 3 of 4, or provide on a separate grading plan, that references the table located on Sheet 1 for all depressed curb areas inlet invert elevations and dimensions that are to be constructed. All rock riprap slopes must meet the recommendations that are included within the required soils engineering report.

23) DS Sec.11-01.4.1.C.4: Revise Detail #8 to call out the appropriate detail (Detail 4/4) associated with the weir outlet detail for Basin B. Call out all riprap D50 size and thickness. Provide spot elevation for the basin bottom.

24) DS Sec.11-01.4.1.C.6: Provide a detail for the 1:1 slope that is shown at the bend of the proposed channel. Recommendations of the soils engineering report must be incorporated within the detail.

25) DS Sec.11-01.4.1.C.7: Provide a General Note referencing the Geotechnical Report, provide the name, address, job number, date, and phone numbers of the firms or individuals who prepared the report. State that the grading plan shall comply with recommendations within the report as well as any subsequent geotechnical addenda.

26) DS Sec.11-01.4.1.F: Provide typical lot grading details, show minimum side and rear setbacks, and building setbacks to the detention and retention basins and swales per geotechnical report. Provide detailed cross sections for each perimeter, fully labeled and dimensioned.


DRAINAGE REPORT:

27) DS Sec.2-02.2.1.A.15: Clarify or revise the drainage report for the parcel showing that the developed discharge for the 2, 10, and 100-year flow events are less than the existing corresponding discharge values with a 15 % reduction. The proposed drainage report shows a 26.5 cfs increase in discharge for developed conditions into the Country Club right-of-way. The drainage report must meet the minimum standards for development outlined in the Stormwater Detention/Retention Manual.

28) DS Sec.10-02.2.3.1.6.A: Revise or clarify Paragraph 3 on Page 3 of the drainage report to state that the 100-year developed discharge will be reduced by 15% from the existing discharge along with the 5-year threshold retention provided. Revise the drainage report to meet the minimum standards for development within a Critical Basin.

29) DS Sec. 3-01.4.4.F: Provide a revised drainage report showing scupper calculations that demonstrate that the 10-year flood flow from the roof drainage is contained under the sidewalk. Provide details and dimensions in plan view for all proposed scuppers.


GEOTECHNICAL REPORT:

30) DS Sec.10-01.III.3.5.1.3.a, 10-02.14.2.6: Provide a Geotechnical Report Evaluation that addresses the following:

a) soils report should provide conformance with DS Section 10-02.14.2.6 regarding 30-foot boring for basin, and provide a discussion of the potential for hydro-collapsible soils and any recommendation for setbacks from building to proposed retention/detention basins, water harvesting basins and constructed channel.

b) the soils report shall provide identification / assessment of any potentially hazardous geotechnical areas, and state any geotechnical recommendations and whether there are special provisions for the soil preparation for this development.

c) provide slope stability recommendations for any proposed constructed slopes.

d) provide percolation rates for retention/detention basins for 5-year threshold retention.


STORMWATER POLLUTION PREVENTION PLAN:

31) Arizona Pollutant Discharge Elimination System (AZPDES) requirements are applicable to this project. Stormwater Pollution Prevention Plans (SWPPP) and text addressing stormwater controls for all areas affected by construction activities related to this development will be required with the re-submittal. For further information, visit www.adeq.state.az.us/environ/water/permits/stormwater.html.


GENERAL COMMENTS:

Please provide a revised site plan, revised grading plan, revised drainage report, a geotechnical engineering report, and a SWPPP that address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon resubmittal of the site plan, grading plan, drainage report, geotechnical report, and SWPPP reviews. Site plan must be approved prior to grading plan approval.

If you have any questions, or to schedule an appointment, I can be reached at 791-5550, extension 1189.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
09/26/2006 SUE REEVES REJECT SHELF Completed