Permit Number: T06CM03767
Parcel: 107110080

Address:
3149 N 1ST AV

Review Status: Active

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM03767
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
07/19/2006 TERRY STEVENS ZONING REVIEW Approved
07/19/2006 JASON GREEN ENGINEERING REVIEW Approved
08/07/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM03767 7/19/06

1. Revise the font size used to a minimum of 1/8 inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. From the electrical plans, the new generator is to be diesel powered. However, the title sheet calls for a new propane tank. Please clarify scope of work. If a propane tank is to be used in conjunction with the electrical, address the requirements of Chapter 5 of the NEC for Classified Locations.