Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T06CM03767
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/19/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/19/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 08/07/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM03767 7/19/06 1. Revise the font size used to a minimum of 1/8 inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. From the electrical plans, the new generator is to be diesel powered. However, the title sheet calls for a new propane tank. Please clarify scope of work. If a propane tank is to be used in conjunction with the electrical, address the requirements of Chapter 5 of the NEC for Classified Locations. |