Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM03765
Parcel: 12217302A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03765
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2006 TERRY STEVENS ZONING REVIEW Approved
06/27/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the ventilation calculations. The amount of outside air to be introduced is ambiguous and the VAV system does not appear to have been taken into account with the ASHRAE 62.1-2004 calculations.
06/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/27/2006 ROBERT SHERRY WATER REVIEW Approved
06/27/2006 DAVE MANN FIRE REVIEW Approved
06/27/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
06/27/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify how P-3 is to be connected to the building drain (i.e. add a riser diagram).
06/30/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
07/05/2006 GERRY KOZIOL WWM REVIEW Completed
07/05/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review