Review Details: COMMERCIAL TI
Permit Number - T06CM03765
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/27/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/27/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the ventilation calculations. The amount of outside air to be introduced is ambiguous and the VAV system does not appear to have been taken into account with the ASHRAE 62.1-2004 calculations. |
| 06/27/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 06/27/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify how P-3 is to be connected to the building drain (i.e. add a riser diagram). |
| 06/27/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/27/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/27/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/30/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/05/2006 | GERRY KOZIOL | WWM | REVIEW | Completed | |
| 07/05/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |