Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM03724
Parcel: 11106245A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM03724
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2007 MADARA ENGINEERING 2ND PARTY REVIEW REVIEW Denied MADARA Engineering, Inc.
4545 E. Shea Blvd. Suite 207, Phoenix, AZ 85028, phone (602) 493-1963, fax (602) 493-1967

Date: September 14, 2007
To: Douglas Harvey
4945 N. Calle Bendita
Tucson, AZ 85718
Phone: (520) 299-2236
Project name: 3250 E. Blacklidge Dr.
Permit #: TO6-CM03724
Structure: 1 story SFR
Occupancy: R-3/ U
Occupant load: 8
Construction Type: V-B
Area S.F.: 2825 SF Project number: 18-6027-04


The second submittal plans for the above referenced project are in the process of Architectural, Structural, Plumbing, Mechanical and Electrical plan review for compliance with the City of Tucson ordinances and applicable codes. Corrections required are noted below. All corrections must be made to the original drawings and new complete and revised sets resubmitted along with a written response to each of the items listed below to facilitate a shorter back-check time.

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical review. These disciplines were checked only to the extent allowed by the documents provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

ARCHITECTURAL COMMENTS
Provide a complete Framing Plan for layout and support of ceiling joists. Specify grade, species, size and spacing of all ceiling joist framing members. Ref. IRC Section R106.

STRUCTURAL COMMENTS
Sheet A3
Clarify note for horizontal drag struts at re-entrant corner for lateral shear at roof to be transferred to the vertical shear walls as this load cannot be deferred since it does not apply to truss, but blocking or strap. Please recheck applicability if the new 1/A3 detail.

Sheet A6
Complete framing details including the provisions for wall anchorage to roof diaphragm per IBC 1604.8.1 or IRC R606.8.2.1. See roof Details 4, 5, 8. Note is provided, but the element is not drawn.

PLUMBING COMMENTS
Clarify if work shop water heater remains in existing location. Address T and P drain and safe pan with drain as appropriate.

MECHANICAL COMMENTS – Mechanical portion has been reviewed and approved;

ELECTRICAL COMMENTS:
Denote disconnect panel at workshop to be labeled as suitable for use as service equipment or clarify feeder to be 3 32 with # 8 bond.
Provide switch or automatically controlled light at exterior door near bath at work shop. Provide cut sheets for all exterior light fixtures at both buildings for use in evaluation of outdoor lighting code compliance.
Clarify voltage of water heater at workshop (120 or 240) and revise circuit 8 in panel as necessary along with revision to conductor sizes as appropriate. Show disconnect for this water heater. Ref. IRC Table E4001.5.
Provide 20-amp branch circuit for workshop bathroom receptacle that supplies no other loads. Ref. IRC E3603.4.

Should you have any inquires regarding this letter, please do not hesitate to contact the Plan reviewer at (602) 493-1963.
MADARA Engineering for the CITY OF TUCSON

By:
Michael Hundley
Vice-President
09/20/2007 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit evaluation

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
09/27/2007 SUE REEVES REJECT SHELF Completed