Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM03714
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM03714
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The submitted drawing set does not include the revised sheet M5.1.
10/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The submitted drawings do not show how the sump pump has been changed. The use of the oil-smart switch for the elevator sump pump will require an approved appeal from the building official. Reference Section 301.2, UPC 2003.
2. The submitted drawings do not show how the sump pump has been changed. Clarify the missing portion of detail 1/P2.2 (relating to the sump pump discharge). Reference Section 103.2.3, UPC 2003.
3. A combination waste and vent system is not self-scouring and as such, it is not suitable for floor drains in mammal holding pens. Reference Section 910.1 and Section B1, UPC 2003.
10/06/2006 WILDAN 2ND PARTY REVIEW REVIEW Approved
10/16/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied An approved site plan is required prior to building plan approval. The site plan must be approved by zoning, fire, landscape and engineering.
10/17/2006 PATRICIA GEHLEN ZONING REVIEW Denied Signed administrative waiver needed.
10/17/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please note that the Structural Plans Examiner has been given notice to verify that the weight of the 112.5 KVA Transformer installed in Room 204 has been accounted for in Structural calculations. If this has been coordinated, disregard. DID NOT FIND IN CURRENT SUBMITTAL.
2. For all lighting poles greater than 20' in height, detail and calculations for pole and foundation shall be prepared and sealed by a Registered Structural Engineer. DID NOT FIND IN CURRENT SUBMITTAL.
3. Panel PV appears on the Single Line Diagram, but is has been removed from this project. Photovoltaic conductors on Single Line Diagram and Photovoltaic Riser Diagram do not correspond.
4. According to the technical support staff at Sunny Boy, (1.530.273.4895) the outputs from the 3 inverters must each be terminated in a single pole breaker, not a 3-pole breaker; this would appear to be consistent with NEC 690.64 (B) (1). I spoke with Antonio, 10/17/06. He referred me to the Installation Guide, most specifically pages 4-4 and 4-5.
5. At the PV Disconnects, specify the marking required by NEC 690.53. Provide the EXACT WORDING on the plans. This instruction for the contractor could be added to the Electrical Keynote on Sheet e5.1.
6. At the Panel DP, specify the marking required by NEC 690.54. Provide the EXACT WORDING on the plans. We have not enforced this very closely at locations where the inverter and DC disconnecting means are in sight of the panel where the interconnection takes place because of the requirements of 690.53, but it is necessary in this configuration.
7. On the SES Arrangement, Sheet e1.1, it appears that the wording "Panel D1 Disconnect" should read: "Panel DP Disconnect."
8. On Sheet e1.2, it appears that Keynote 3 should be placed by the proper piece of equipment on the PV Inverter Arrangement. This would also satisfy the requirements of Comment #27 from the previous submittal.
9. On Sheet e5.1, the inverter parameters have the wording "INPUT VOLTAGE" twice.
10. Regardless of the instruction in Keynote 7 to keep the Grounding Electrode Conductor unspliced throughout the installation, the diagram of the PV Service Disconnect on Sheet e5.1 appears to allow this. Please clarify.
10/25/2006 GERRY KOZIOL WWM REVIEW Denied DEQ requirements- appears graywater discharger is over 400 GPD & not residential- therefore a Type 3 general permit is required as issued by ADEQ- see attached.

WW cannot drain elevator pit to sewer. needs wastewater 8th floor credit evaluation if applicable.
11/07/2006 MARTY DUPONT ADA REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/09/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
11/09/2006 SUE REEVES REJECT SHELF Completed