Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM03710
Parcel: 126050730

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM03710
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/06/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. PROVIDE COMPLETE DIMENSIONS AND FIXTURE LOCATIONS FOR ACCESSIBILE TOILET ROOM.
S2. PROVIDE COMPLETED CODE REVIEW CHECKLIST.
S3. PROVIDE A COPY OF THE LAST CITY APPROVED FLOOR PLAN.
S4. CLARIFY FIRE SPRINKLERS.
07/06/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide structural details of the mounting hardware and existing wall materials to clarify detail 201/P-2.0
07/06/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03710 7/6/06

1. Water Heater is 3-phase according to Sheet P-2.1. Is single phase on Electrical plans. Coordinate with Plumbing and clarify. Note: Mechanical Engineer will probably have to change his specification, because 3-phase power does not appear to be currently available at this location.