| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/06/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. PROVIDE COMPLETE DIMENSIONS AND FIXTURE LOCATIONS FOR ACCESSIBILE TOILET ROOM. S2. PROVIDE COMPLETED CODE REVIEW CHECKLIST. S3. PROVIDE A COPY OF THE LAST CITY APPROVED FLOOR PLAN. S4. CLARIFY FIRE SPRINKLERS. |
| 07/06/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide structural details of the mounting hardware and existing wall materials to clarify detail 201/P-2.0 |
| 07/06/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM03710 7/6/06 1. Water Heater is 3-phase according to Sheet P-2.1. Is single phase on Electrical plans. Coordinate with Plumbing and clarify. Note: Mechanical Engineer will probably have to change his specification, because 3-phase power does not appear to be currently available at this location. |