Permit Number: T06CM03710
Parcel: 126050730

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03710
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
06/23/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003.
2. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2003.
06/23/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. If the water service pressure exceeds 80 PSI, provide a pressure reducer for the water service
2. Clarify how the water heater is to be supported from the wall.
06/23/2006 ROBERT SHERRY WATER REVIEW Approved
06/23/2006 DAVE MANN FIRE REVIEW Approved
06/23/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
07/06/2006 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/06/2006 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
07/06/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/10/2006 AOLIVO1 WWM REVIEW Needs Review