Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03710
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/23/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/23/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003. 2. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2003. |
| 06/23/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. If the water service pressure exceeds 80 PSI, provide a pressure reducer for the water service 2. Clarify how the water heater is to be supported from the wall. |
| 06/23/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/23/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/23/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 07/06/2006 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/06/2006 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/06/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/10/2006 | AOLIVO1 | WWM | REVIEW | Needs Review |