Permit Number: T06CM03698
Parcel: 116112200

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM03698
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03698 10/18/06

1. Specify the conduit type and depth of burial for the conduit going underground from the inverter to the Sun Share Meter. Reference NEC Chapter 3 for conduit type, and NEC Table 300.5 for Minimum Cover Requirements.
2. Specify the plaques required by NEC 690.56 (B). Provide the exact wording on the submitted material. For example, "A plaque shall be placed at the inverter with the following wording: Photovoltaic disconnect. Main service panel is located north of this fence."
"A plaque shall be placed at the main service panel with the following wording: Photovoltaic system interconnected here. Photovoltaic disconnect is located on the south side of block fence."
3. Provide the size of the DC grounding electrode conductor. Reference NEC 250.166 (B).
4. Both grounding electrodes shall be connected. Reference NEC 250.50.
5. Provide the size for the Main Circuit Breaker. Reference NEC 690.64 (B) (2).

Final Status

Task End Date Reviewer's Name Type of Review Description
10/23/2006 BETH GRANT OUT TO CUSTOMER Completed