Permit Number: T06CM03640
Parcel: Unknown

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T06CM03640
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2006 PETER MCLAUGHLIN ZONING REVIEW Denied Approved site plan required.
06/30/2006 CRAIG GROSS PLANNING-CITY HALL REVIEW Denied Demonstrate compliance with Special Exception conditions e and f.
07/07/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/13/2006 JAY HOGAN COMMUNICATIONS REVIEW Approved
07/19/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied STRUCTURAL REVIEW COMMENTS

DATE: 7/25/06
ACTIVITY NUMBER: T06CM03640
PROJECT NAME: Cell Site
PROJECT ADDRESS:7167 E. Escalante
ARCHITECT / ENGINEER: M3 Engineering.
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1) Clarify connections for antennas. Justify connections are adequate for the additional loads applied by antennas.
2) Clarify location of property lines in reference to equipment enclosure and TEP pole.
3) Clarify weight of equipment shown on the equipment pad.
4) Provide manufacturer cut sheets / specifications for pre-manufactured slab.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
10/12/2006 SUE REEVES REJECT SHELF Completed