Review Details: COMMERCIAL TI

Permit Number - T06CM03606
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2006 TERRY STEVENS ZONING REVIEW Approved
06/28/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the refrigerant monitoring system with the electrical design.
2. Show the size, route and termination of any pressure relief devices for the refrigeration equipment.
06/28/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/28/2006 DAVE MANN FIRE REVIEW Denied Need controls and signage per International Fire Code Section 606.
07/21/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Needs Review
07/21/2006 CAGUILA1 WWM REVIEW Needs Review
07/21/2006 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/21/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review