Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03606
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/28/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
06/28/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the refrigerant monitoring system with the electrical design. 2. Show the size, route and termination of any pressure relief devices for the refrigeration equipment. |
06/28/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/28/2006 | DAVE MANN | FIRE | REVIEW | Denied | Need controls and signage per International Fire Code Section 606. |
07/21/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
07/21/2006 | CAGUILA1 | WWM | REVIEW | Needs Review | |
07/21/2006 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
07/21/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |