Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T06CM03603
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/21/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/22/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | DATE: June 23, 2006 SUBJECT: Construction of 2 Ramada's and Concrete, Brick Decomposed Granite Pathway- Engineering Review ADDRESS: 5901 S Fiesta Ave, Tucson Arizona 85706 PROPERTY OWNER: COT Parks and Recreation Department LOCATION: T15S R13E Section 12, Mission Heights No 5 (B24, P14) Public Park REVIEWER: Jason Green, CFM ACTIVITY NUMBER: T06CM03603 SUMMARY: The Floodplain Use Permit and site plan were received and reviewed by Engineering Division. The Floodplain Use Permit application (T06OT01614) and site plan (T06CM03603) will be issued for 2 open sided Ramada and the construction of a concrete, brick, and stabilized decomposed granite pathway. Engineering Division recommends approval of the Floodplain Use Permit and site plan. CONDITIONS OF PERMIT: The associated improvements are with permit activity number T06OT01614 (Floodplain Use Permit) and T06CM03603 (site plan). The applicant attests to the fact that the plans and documents submitted represent all of the improvements that will be constructed and are included in the construction plans and/or documents herewith. This permit is specific to the Ramada construction and the construction of a concrete, brick, and stabilized decomposed granite pathway as shown on this site plan. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit. Copies of the site plan/permit documents shall be kept in a readily accessible location on site at all times. If you have any questions, I can be reached at 791-5550, extension 1189. Jason Green, CFM Senior Engineer Associate Engineering Division Development Services |
| 07/20/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide structural plans and details for the new ramada. Also provide engineering calc`s. |
| 07/27/2006 | MARTY DUPONT | ADA | REVIEW | Denied | This project has been reviewed by the City of Tucson Office of Equal Opportunity Programs for compliance with the Department of Justice 28 CFR Part 36 ADA Standards for Accessible Design, Revised July 1, 1994. 1) Provide the running & cross slope of the new concrete walk. Running slope not to exceed 5% and cross slope not to exceed 2% §4.3. Provide a passing space as required by §4.3.4. If runing slope exceeds 5% it shall be considred a ramp and the requirements of §4.8 shall apply. 2) Provide a transition detail between changing surface materials. Changes in level up to 1/4" are allowed without treatment §4.5.2. 3) Demonstrate that the running slope along the entire length of the stabalized dg path does no exceed 5% and the cross slope does not exceed 2%. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/01/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 08/01/2006 | SUE REEVES | REJECT SHELF | Completed |