Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2006 MARTIN BROWN FIRE REVIEW Approved
04/04/2006 HEATHER THRALL ZONING REVIEW Approved
05/24/2006 JOSE ORTIZ ENGINEERING REVIEW Approved
06/16/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/16/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06BU00771 .. 5890 SOUTH AVENIDA SELVA DE OCOTE .. TRES PUEBLOS PARK .. DGL .. 1ST REVIEW COMMENTS .. 6/13/06 ..
.. T06BU00772 .. 5935 SOUTH AVENIDA RIBERO .. TRES PUEBLOS PARK .. DGL .. 1ST REVIEW COMMENTS .. 6/13/06 ..


TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.

S1. Provide a complete set of drawings for review, this submittal contains drawings R1, R2, R3, R7 of 7 and a drawing for a 12' x 12' ramada.
S2. Provide completed Commercial Plan Submittal Checklist by Architect of Record, including: Signature of Architect/Engineer of Record, Registration number of Registrant of Record, Date form is completed, Job Address and Acknowledge items listed on this Checklist are in this Submittal by checking the adjacent square. See DSD website : www.tucsonaz.gov/dsd, for form.
S3. Provide completed Code Review Checklist, as required by 1997 Uniform Administrative Code Section 302.1, including: Job Address, Architect, Signature, Date, Summary of Governing Regulations, General Building Summary and Allowable Area Calculation. See DSD website : www.tucsonaz.gov/dsd, for form.
S4. Show accessible route on drawings, per International Building Code Section 11 and ANSI A117.1-2003ed :
1. Identify location of accessible route on drawing R1, per IBC Sec 1104 and ANSI Sec 4.
2. Show accessibility to recreational facilities, including basketball court, pet waste station, trash cans, (8'x8' and 12'x12')ramadas, BBQs, picnic tables, benches, Large Play Structure, Small Play Structure, other equipment provided per IBC Sec 1109.14.3.
3. Show location, dimensions and specifications for detectable warnings per IBC Sec 1109.9 and ANSI A117.1 Sec 705.
4. Specifications and location of accessible drinking fountains per IBC Sec 1109.5 and ANSI Sec 602.
5. Ramps, landings, slopes, grade changes and maneuvering clearances.
S5. Submit two sets of shop drawings and calculations, stamped and signed by an Arizona Registered engineer, shop drawings shall be reviewed by and bear the approval of the Engineer or Architect of Record prior to submission to the City of Tucson , Development Services Department for approval prior to erection for the:
1. Pet waste station.
2. Trash cans.
3. (8'x8' and 12'x12')Ramadas.
4. BBQs.
5. Picnic tables.
6. Drinking fountains.
S6. Provide Special Inspection as required by the 1997 Uniform Administrative Code as amended and adopted by the City of Tucson, Section 306:
1. High strength bolting.
2. Shop welding.
S7. Provide addressing per Pima County Addressing Ordinance and IBC section 501.2 on the drawings.
S8. Dimensionally locate the structures on the Site Plan by from two adjacent Property Lines.


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd.
06/19/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Plans indicate irrigation controls.(Where does this circuit come from? Please provide the electrical information on these plans include any lighting-receptacles etc.)
06/22/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a plumbing design for the project. Reference Section 103.2.3, UPC 2003.
2. The applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments.