Permit Number: T06CM03567
Parcel: 121136010

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM03567
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/22/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied I REVIEWED THIS PROJECT FOR THE CORRECTIONS TO
THE DRAWINGS PERTAINING TO CHRISTY'S PRIOR COMMENTS:
(1)PROVIDE ACCESSIBILITY EACH RESTROOM PER ANSI A117.1 2003.
2) CLARIFY DIMENSIONS FOR TWO DOOR IN A SERIES PER ANSI A117.1 2003.
3) RECEPTION COUNTER PROVIDE PER ANSI A117.1 2003 904.3.)
THESE QUESTIONS REMAIN:
RE #1, DIMENSIONS LOCATING WC AT 18" FROM SIDEWALL REQUIRED PER DAVID MANN COT-BUILDING OFFICIAL RE:FEDERAL AUDIT W/NO VARIANCE, LOCATION OF FLUSH VALVE REQUIRED TO BE ON OPEN SIDE OF WC PER ANSI SEC 604.6, DOOR TO MEN'S TOILET ROOM DOES NOT MEET FORWARD APPROACH REQUIREMENTS OF ANSI FIG 404.2.3.4 (C), CHECK DIMENSIONS OF TOILET ROOMS ON PLAN TO SEE IF THE MATCH ELEVATIONS ON DRAWING 2.2.
RE #2. DOOR IN CORRIDOR REQUIRED TO SWING CLEAR OF APPROACH AREA TO MEN'S TOILET ROOM PER ANSI SEC 404.5.
RE#3. SHOW REQUIRED CLEARANCES PER ANSI SEC 904.3 AT COUNTER , INCLUDING KNEE AND TOE CLEARANCES PER ANSI 306.
06/26/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review