Permit Number: T06CM03567
Parcel: 121136010

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03567
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2006 AKLAPPE1 BUILDING-COMMERCIAL REVIEW Needs Review
06/21/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The water pipe sizing is not supported by the pressure calculations. Revise the pipe sizing per Section 610.1, UPC 2003.
06/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide specifications and operating parameters for the exhaust fans, EF-1 and EF-2.