Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM03566
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. PROVIDE SECOND EXIT FROM SHOWROOM BASED ON OCCUPANT LOAD 2467 SF/ 30 = 82. 2ND EXIT MAY NOT EXIT THROUGH STORAGE. S2. DETAIL CONNECTION OF TOP OF STUD WALLS TO STRUCTURE ABOVE. S3. PROVIDE PROJECT VALUATION. |
| 06/20/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The integral thermostat for the water heater shall not be used to provide anti-scald protection for the lavatories. Reference Section 414.1, UPC 2003. |
| 06/20/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/23/2006 | JMORALE1 | WWM | REVIEW | Needs Review | |
| 06/23/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |