Permit Number: T06CM03566
Parcel: 13204008A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM03566
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. PROVIDE SECOND EXIT FROM SHOWROOM BASED ON OCCUPANT LOAD 2467 SF/ 30 = 82. 2ND EXIT MAY NOT EXIT THROUGH STORAGE.
S2. DETAIL CONNECTION OF TOP OF STUD WALLS TO STRUCTURE ABOVE.
S3. PROVIDE PROJECT VALUATION.
06/20/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The integral thermostat for the water heater shall not be used to provide anti-scald protection for the lavatories. Reference Section 414.1, UPC 2003.
06/20/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/23/2006 JMORALE1 WWM REVIEW Needs Review
06/23/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review