Permit Number: T06CM03566
Parcel: 13204008A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03566
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/15/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust to insure that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003.
06/15/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
06/15/2006 ROBERT SHERRY WATER REVIEW Approved
06/15/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
06/19/2006 TERRY STEVENS ZONING REVIEW Approved
06/20/2006 DROBEY1 WWM REVIEW Needs Review
06/20/2006 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
06/20/2006 DAVE MANN FIRE REVIEW Approved
06/20/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review