Permit Number: T06CM03545
Parcel: 119421670

Review Status: Active

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM03545
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06BU01185 .. 1701 WEST IRVINGTON PLACE .. CASITAS DEL SOL ESTATES COMMON AREA 'B' .. DGL .. 1ST REVIEW COMMENTS .. 6/14/06 ..
.. T06BU01186 .. 1701 WEST IRVINGTON PLACE .. CASITAS DEL SOL ESTATES COMMON AREA 'B' .. DGL .. 1ST REVIEW COMMENTS .. 6/14/06 ..


TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.

S1. Provide a set of drawings for review that has property lines, finish grades, streets identified, location of structures on the property, this submittal contains drawings landscaping drawings L-1 thru L-13 and a drawing for a 10' x 10' ramada.
S2. Provide completed Commercial Plan Submittal Checklist by Architect of Record, including: Signature of Architect/Engineer of Record, Registration number of Registrant of Record, Date form is completed, Job Address and Acknowledge items listed on this Checklist are in this Submittal by checking the adjacent square. See DSD website : www.tucsonaz.gov/dsd, for form.
S3. Provide completed Code Review Checklist, as required by 1997 Uniform Administrative Code Section 302.1, including: Job Address, Architect, Signature, Date, Summary of Governing Regulations, General Building Summary and Allowable Area Calculation. See DSD website : www.tucsonaz.gov/dsd, for form.
S4. Show accessible route on drawings, per International Building Code Section 11 and ANSI A117.1-2003ed :
1. Identify location of accessible route on drawings, per IBC Sec 1104 and ANSI Sec 4.
2. Show accessibility to recreational facilities, including: trash cans, ramadas, picnic tables, benches, Sof-Fall Play Surface, other equipment provided per IBC Sec 1109.14.3.
3. Show location, dimensions and specifications for detectable warnings per IBC Sec 1109.9 and ANSI A117.1 Sec 705.
4. Specifications and location of accessible drinking fountains per IBC Sec 1109.5 and ANSI Sec 602.
5. Ramps, landings, slopes, grade changes and maneuvering clearances.
S5. Submit two sets of shop drawings and calculations, stamped and signed by an Arizona Registered engineer, shop drawings shall be reviewed by and bear the approval of the Engineer or Architect of Record prior to submission to the City of Tucson , Development Services Department for approval prior to erection for the:
1. Pet waste station.
2. Trash cans.
3. 10' x 10' Ramada.
4. BBQs.
5. Picnic tables.
6. Drinking fountains.
S6. Provide Special Inspection as required by the 1997 Uniform Administrative Code as amended and adopted by the City of Tucson, Section 306:
1. Shop welding.
S7. Provide addressing per Pima County Addressing Ordinance and IBC section 501.2 on the drawings.
S8. Dimensionally locate the structures on the Site Plan by from two adjacent Property Lines.


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd.
06/15/2006 LOREN MAKUS ENGINEERING REVIEW Approved
06/15/2006 DAVE MANN FIRE REVIEW Approved
06/15/2006 HEATHER THRALL ZONING REVIEW Approved
06/16/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Plans indicate irrigation controls.(Where does this circuit come from? Please provide the electrical information on these plans include any lighting-receptacles etc.)
06/16/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2006 SUE REEVES REJECT SHELF RECEIVED