Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM03541
Parcel: 141153550

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T06CM03541
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2006 HEATHER THRALL ZONING REVIEW Approved
06/14/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
06/14/2006 AOLIVO1 FIRE REVIEW Needs Review
06/14/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed