Permit Number: T06CM03428
Parcel: 12407040B

Address:
745 E 9TH ST

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM03428
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03428 6/23/06

1. Please specify that Fixture A be of FCO lighting distribution. Reference Tucson Lighting Code 5.1.2 and 2003 IECC 805.6. Such fixture is exempt from the lumen count as FCO installed under such canopies, but the plans need to be explicit in this regard: clearly, owner-selected does not cut it.
3. No new WH indicated on Plumbing plans. Please coordinate with ME and clarify. Mechanical/Plumbing Plans Examiner has verified that such coordination is necessary, and has removed his approval from the plans. If a WH of the same electrical characteristics is to replace one which is existing, it is necessary at minimum to indicate such replacement on the electrical plans.
06/23/2006 LINDA BUCZYNSKI PLUMBING-COMMERCIAL REVIEW Needs Review