Permit Number: T06CM03428
Parcel: 12407040B

Address:
745 E 9TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03428
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2006 HEATHER THRALL ZONING REVIEW Approved
06/09/2006 PAUL MACHADO ENGINEERING REVIEW Approved
06/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03428 6/20/06

1. The disconnects for the new ACs are NF on the Power Plan, but are supplied with FRN-R60s on the Riser Diagram. Please eliminate the reference "NF" on the Power Plan.
2. Please specify that Fixture A be of FCO lighting distribution, and that they shall not be incandescent. Reference Tucson Lighting Code 5.1.2 and 2003 IECC 805.6.
3. No new WH indicated on Plumbing plans. Please coordinate with ME and clarify.
06/20/2006 DAVE MANN FIRE REVIEW Approved
06/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/21/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
06/21/2006 ROBERT SHERRY WATER REVIEW Approved
06/21/2006 RSHERRY1 WWM REVIEW Passed
06/23/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review