Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03428
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 06/09/2006 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 06/20/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM03428 6/20/06 1. The disconnects for the new ACs are NF on the Power Plan, but are supplied with FRN-R60s on the Riser Diagram. Please eliminate the reference "NF" on the Power Plan. 2. Please specify that Fixture A be of FCO lighting distribution, and that they shall not be incandescent. Reference Tucson Lighting Code 5.1.2 and 2003 IECC 805.6. 3. No new WH indicated on Plumbing plans. Please coordinate with ME and clarify. |
| 06/20/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/21/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/21/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/21/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/21/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 06/23/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review |