Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2007 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
01/23/2007 GBONILL1 WWM REVIEW Needs Review
06/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03408 6/8/06

1. Show load calculations for electrical load on panel.
2. Provide an electrical line diagram with electrical service, grounding electrode system, panel(s), disconnecting means, conductor and conduit.
3. Specify conduit and conductor size and type.
4. Provide TEP available fault current at electrical service.
5. Provide fault current rating of panel.
6. Demonstrate that AFC at panel does not exceed its fault current rating.
06/08/2006 ROBERT SHERRY WATER REVIEW Approved
06/08/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the design of the waste and vent system for the restroom with the inclusion of riser diagrams. Show also the locations of all cleanouts.
2. Clarify the note, "to condensate drain line O.H."
3. Show the size, route, and termination of the T&P relief piping from the water heaters.
4. Show how the temperature of the hot water is to be limited to 110 degrees Fahrenheit at the lavatories.
06/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide mechanical plans; show ventilation requirements per Section 403.3, IMC 2003.
06/12/2006 HEATHER THRALL ZONING REVIEW Approved
06/12/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
06/12/2006 MARTIN BROWN FIRE REVIEW Approved