Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03408
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/23/2007 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/23/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 06/08/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM03408 6/8/06 1. Show load calculations for electrical load on panel. 2. Provide an electrical line diagram with electrical service, grounding electrode system, panel(s), disconnecting means, conductor and conduit. 3. Specify conduit and conductor size and type. 4. Provide TEP available fault current at electrical service. 5. Provide fault current rating of panel. 6. Demonstrate that AFC at panel does not exceed its fault current rating. |
| 06/08/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/08/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the design of the waste and vent system for the restroom with the inclusion of riser diagrams. Show also the locations of all cleanouts. 2. Clarify the note, "to condensate drain line O.H." 3. Show the size, route, and termination of the T&P relief piping from the water heaters. 4. Show how the temperature of the hot water is to be limited to 110 degrees Fahrenheit at the lavatories. |
| 06/08/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide mechanical plans; show ventilation requirements per Section 403.3, IMC 2003. |
| 06/12/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 06/12/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 06/12/2006 | MARTIN BROWN | FIRE | REVIEW | Approved |