Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T06CM03381
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2006 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | comments on card |
| 09/19/2006 | PATRICIA GEHLEN | ZONING HC SITE | REVIEW | Denied | comments on card. |
| 09/20/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | The large retail, dollar store and Fry's are not allowed unlimited area without sprinklers. |
| 09/25/2006 | ANDREW CONNOR | NPPO | REVIEW | Approved | |
| 09/25/2006 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Revise note 2 exception on sheet 1 of the landscape plan. Dust control is required for the bottom of the basin. LUC 3.7.2.7 2. New tree planting areas are required to comply with LUC 3.7.2.3. An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree. Revise the site and landscape plans as necessary to provide inside dimensions. 3. Verify the location of the property line along Pantano Rd is correctly depicted on the landscape plan. DS 2-07.2.0 |
| 10/05/2006 | ANY | ENGINEERING | REVIEW | Approved |