Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03372
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2006 | HEATHER THRALL | ZONING | REVIEW | Needs Review | |
| 06/07/2006 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/07/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM03372 6/7/06 1. Clarify mounting of tech lights. Sheet C-2 calls for them to be wall-mounted. Sheet C-5 provides a detail for pole-mounting. 2. Eliminate the redundant #4 GROUND between the Meter and the Main Disconnect. 3. Please clarify your specification of fault current rating. Main disconnect is rated at 14 KAIC, but its downstream ALL-IN-ONE is rated 65/10. |
| 06/07/2006 | GBONILL1 | WATER | REVIEW | Needs Review | |
| 06/07/2006 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/07/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 06/07/2006 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 06/07/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 06/07/2006 | DAVE MANN | FIRE | REVIEW | Approved |