Permit Number: T06CM03372
Parcel: 10711136A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03372
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2006 HEATHER THRALL ZONING REVIEW Needs Review
06/07/2006 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
06/07/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03372 6/7/06

1. Clarify mounting of tech lights. Sheet C-2 calls for them to be wall-mounted. Sheet C-5 provides a detail for pole-mounting.
2. Eliminate the redundant #4 GROUND between the Meter and the Main Disconnect.
3. Please clarify your specification of fault current rating. Main disconnect is rated at 14 KAIC, but its downstream ALL-IN-ONE is rated 65/10.
06/07/2006 GBONILL1 WATER REVIEW Needs Review
06/07/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
06/07/2006 GBONILL1 WWM REVIEW Needs Review
06/07/2006 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
06/07/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
06/07/2006 DAVE MANN FIRE REVIEW Approved