Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM03356
Parcel: 13414018N

Address:
7501 E 22ND ST

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T06CM03356
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
06/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
2. For all poles over 25' in height, provide details and calculations for both pole and foundation, sealed by a Registered Structural Engineer.
3. Sheet E0.1 contains Code-related design information and shall be sealed.
4. Ckts HA-19,21, HA-23,25, HA-27,29, HA-18,20, and HA-22,24, at 8000 VA each, would draw 36A at continuous loading. The 20A circuits would be insufficient. However, please note that if the intent is to put 4-1000W luminaires on each circuit, this would account for 2000VA per phase, not 4000.
5. Since the plan set is to be modified, please revise the One-Line Diagram to incorporate the change indicated in the letter from the Registrant dated June 15, 2007.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/22/2007 SUE REEVES REJECT SHELF Completed