Permit Number: T06CM03356
Parcel: 13414018N

Address:
7501 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM03356
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
01/04/2007 GERRY KOZIOL WWM REVIEW Completed
01/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate which detail on the structural drawings applies to the water heater support. Detail 5/P2.0 shows how the seismic straps are affixed to the wall but there are no details showing how the water heater shelf is capable of supporting the water heater. Reference Section 103.2.3, UPC 2003.
2. The listing information for the valve was not included in this submittal. Provide listing information for the shower control valve that shows that it complies with the requirements of Section 420.0, UPC 2003, and specifically ASSE 1016.
3. Heat traps are required on both the hot and cold water pipes. Provide the dimensions for the heat traps shown on detail 4/P2.0. Reference Section 804.4, IECC 2003.
4. Revise detail 1/A4.0 to comply with the requirements of Section 1105.2, UPC 2003. Clarify how and where the roof drain and overflow drain are to be terminated. Reference Section 1106.0, UPC 2003.
5. How are the eight roof drains along the south side of the building to be sized and terminated? Reference Section 1106.0, UPC 2003.
01/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/28/2006 HEATHER THRALL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/02/2007 SUE REEVES REJECT SHELF Completed