Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM03356
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/04/2007 | GERRY KOZIOL | WWM | REVIEW | Completed | |
| 01/16/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indicate which detail on the structural drawings applies to the water heater support. Detail 5/P2.0 shows how the seismic straps are affixed to the wall but there are no details showing how the water heater shelf is capable of supporting the water heater. Reference Section 103.2.3, UPC 2003. 2. The listing information for the valve was not included in this submittal. Provide listing information for the shower control valve that shows that it complies with the requirements of Section 420.0, UPC 2003, and specifically ASSE 1016. 3. Heat traps are required on both the hot and cold water pipes. Provide the dimensions for the heat traps shown on detail 4/P2.0. Reference Section 804.4, IECC 2003. 4. Revise detail 1/A4.0 to comply with the requirements of Section 1105.2, UPC 2003. Clarify how and where the roof drain and overflow drain are to be terminated. Reference Section 1106.0, UPC 2003. 5. How are the eight roof drains along the south side of the building to be sized and terminated? Reference Section 1106.0, UPC 2003. |
| 01/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/28/2006 | HEATHER THRALL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/02/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/02/2007 | SUE REEVES | REJECT SHELF | Completed |