Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03356
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The availability and adequacy of the water supply. 3. The design density and the area of operation. |
| 08/18/2006 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/23/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide underground facility tracer wires per ARS 40-360.22. 3. Provide water supply isometrics. Reference Section 103.2.3, UPC 2003. 4. Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the sizes, loads and developed lengths of the piping. Reference Section 103.2.3, UPC 2003. 5. Provide structural details showing how the water heaters are to be mounted above the mop sinks. Reference Section 103.2.3, UPC 2003. 6. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. 7. Provide shower and tub/shower control valves that comply with the requirements of Section 420.0, UPC 2003. 8. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Section 804.4, IECC 2003. 9. The 2-way cleanout shown in Detail 3/P2.0 is in violation of Section 707.6, UPC 2003. 10. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 2003 11. Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference Section 1106.0, UPC 2003. |
| 08/23/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide information on the sequence of operation for the restroom exhausts to show that recirculation of the air from the restrooms will not occur. Reference Section 403.2.1, IMC 2003. 3. Show that the ventilation of the service area complies with the requirements of Section 403.3, IMC 2003 for service stations. |
| 08/23/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/25/2006 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/07/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. It appears that this facility is intended for servicing of vehicles such that it warrants classification according to the requirements of Chapter 5 of the National Electrical Code. 2. On Panel Schedule HA, the wording "14K/36K" should be changed to read "36K/14K." 3. Please change the #6 BOND on the secondary of the 150 KVA transformer to a #2 BOND. Reference NEC Table 250.66. 4. On the One-Line Diagram, please change the 100/3 on Panel HA to read "70/3." That is how the breaker is called out on Panel HA, and #4 is not protected by a 100A OCPD. |
| 09/18/2006 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO MODIFY PLANS- CONNECTION FEES ARE NOT INCLUDED FOR 2 LAVS SHOWN ON FLOOR PLAN, BUT SHOWN ON PLUMBING PLANS. NEEDS WASTEWATER 8TH FLOOR CREDIT EVALUATION. |
| 09/19/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T06CM03356 .. 7501 EAST 22ND STREET .. REMODEL OF TUCSONMOTORSPORTS .. DGL .. 1ST REVIEW COMMENTS .. #S1 THROUGH #S29 .. 9/28/06 .. TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL. Provide a Response Letter, by the Registrant of Record, with the re-submittal addressing each comment listed in Structural Review. S1. Provide completed Commercial Plan Submittal Checklist by Architect of Record, including: Signature of Architect/Engineer of Record, Registration number of Registrant of Record, Date form is completed, Job Address and Acknowledge items listed on this Checklist are in this Submittal by checking the adjacent square. See DSD website : www.tucsonaz.gov/dsd, for form. S2. Provide completed Code Review Checklist, as required by 1997 Uniform Administrative Code Section 302.1, including: Job Address, Architect, Signature, Date, Summary of Governing Regulations, General Building Summary and Allowable Area Calculation. See DSD website : www.tucsonaz.gov/dsd, for form. S3. Revise the font size used on the drawings to a minimum of 1/8 inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. S4. Show required fire-rated walls, note hourly fire-rating as well as location, on site plan #AS1.00, ie: fire-rated wall is required at storage building 'C' due to distance from property line (4'11"), east wall of warehouse building 'B' due to 20' from east property line, etc. S5. Show Building Occupancy and Type of Construction for each structure/building on site per 2003 IBC, also show and locate any imaginary property lines by dimension from adjacent buildings/structures used in your Code Analysis, on the site plan AS1.00. S6. Clarify Code Analysis for separated and non-separated uses per IBC Section 3, explain on drawings individual classifications as to use ( Occupancies), most restrictive Type of Construction, most restrictive code provisions of IBC Sections 403 and 9, show fire separations required by other provisions per IBC Section 302.3.1.Questions re: allowable area per floor, yards and tabular area per Table 503. S7. Provide ventilation at service area per IBC Section 406.6.3. S8. Verify heating equipment installation conforms to IBC Section 406.6.5. S9. Show on drawings building address conforming to IBC Section 501.2 and Pima County Addressing Ordinance. S10. Show fire-rated walls required per IBC Section 7 define type of wall and detail on drawings. S11. In lieu of specifications provide a note on drawing showing finishes conform to IBC Section 8and Table 803.5, including smoke-development and flame-spread rating requirements. S12. Show on drawings that egress doors conform to requirements of IBC Section 1008, including landings per 1008.1.4, 1008.1.5, door hardware per IBC Section 1008.1.8, gates per IBC Section 1008.2, etc. S13. Provide/ verify Exit Signage and Illumination per IBC Section 1011. S14. Since the interior is completely demo'd, all new work under this Building Permit is required to comply fully with 2003 IBC Chap 11 and ANSI A117.1-2003ed. S15. Show/designate on Site Plan AS1.00 the Accessible Route per IBC Section 1104 and show compliance with ANSI A117.1 Chapter 4 on the drawings, from the public way. S16. Indicate Accessible Entrances on Site Plan AS1.00,per IBC Section 1105 and show compliance with ANSI A117.1 Chapter 4 on drawings. S17. Provide calculations on drawings to show number and locations of accessible parking spaces comply with IBC Section 1106 and show compliance with ANSI A117.1 Chapter 5 on the drawings, ref drawing AS1.00. S18. Revise drawings including A7.0, plumbing elements and facilities to comply with IBC Section 1109 and detail on drawings to show compliance with ANSI A117.1-2003ed Chapter 6; ie vertical grab bar at water closet, dimensions at water closet, drinking fountains, sinks, showers, etc. S19. Show on drawings with plans and details how special rooms (dressing rooms, locker room, break room, vending room)and built-in furnishings comply with IBC Section 1109 and ANSI A117.1 Chapters 8 and 9. S20. Show, on drawings, how signage is provided to comply with IBC Section 11 and ANSI A117.1 Chapter 7. S21. Clarify materials used in walls of toilet rooms and showers are of a type that is not adversely affected by moisture per IBC Section 1210, ref drawings A5.1, A7.0 and A10.1. S22. Fully detail installation of E I F S, on metal building wall panels show how this installation conforms to IBC Section 14, structural calculations and ICC ESR-1748. S23.Fully detail installation of simulated/manufactured stone, show how this installation conforms to IBC Section 14, structural calculations and ICC ER-1842. S24. Clarify roof classification of new canopy roof, per IBC Section 1505 and Table 1505.1, minimum roof covering classification of "C" required. S25. Provide architectural details for new canopy and for relocated canopy, (which for Code purposes is also considered new). S26. Provide complete Structural Design for the relocated canopy to show conformance to the 2003 IBC, also provide report or structural review of the canopy to show it conforms to the Structural Design. S27. Submit two sets of shop drawings and calculations, stamped and signed by an Arizona Registered engineer, shop drawings shall be reviewed by and bear the approval of the Engineer or Architect of Record prior to submission to the City of Tucson, Development Services Department for approval prior to erection for: 1. Metal decking. 2. Relocated steel canopy. 3. Steel 'C' joists. S28. Provide Inspection Program as required by the 1997 Uniform Administrative Code as amended and adopted by the City of Tucson, Section 302.5. S29. Provide Special Inspection as required by the 1997 Uniform Administrative Code as amended and adopted by the City of Tucson, Section 306 for: 1. Soils. 2. Epoxy anchors. 3. Reuse of existing canopy. 4. Field welding. 4. Concrete. 5. Bolts in concrete. 6. Reinforcing steel. 7. Expansion anchors. Questions? Call Douglas Laakso, Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson/Development Services Department at 201 North Stone Avenue, Tucson, Arizona, 85701, COT/DSD website : www.tucsonaz.gov/dsd. |
| 09/21/2006 | HEATHER THRALL | ZONING | REVIEW | Denied | Until the site plan has been approved, zoning cannot approve the TI. |