Permit Number: T06CM03352
Parcel: 11618182C

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T06CM03352
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM03352 6/9/06

1. Provide the rating of the panel to which the AC output is to be connected.
2. Provide the rating of the Main overcurrent protective device on the panel to which the AC output is to be connected.
3. Demonstrate compliance with NEC 690.64 (B) (2).
4. Plan view shows 21 panels. TEP model shows 18 panels. Please clarify.
5. Plan view shows panels hanging out over the edge of the roof. This is not an acceptable means of installation.
6. Elevation view shows panels straddling different elevations and hanging out over edges of various roof components. This is not an acceptable means of installation.
06/20/2006 TERRY STEVENS ZONING REVIEW Approved
06/20/2006 TERRY STEVENS NPPO REVIEW Passed
06/20/2006 DANIEL RUSCH BUILDING-RESIDENTIAL REVIEW Approved
06/20/2006 JASON GREEN ENGINEERING REVIEW Approved