Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - RES
Permit Number - T06CM03352
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM03352 6/9/06 1. Provide the rating of the panel to which the AC output is to be connected. 2. Provide the rating of the Main overcurrent protective device on the panel to which the AC output is to be connected. 3. Demonstrate compliance with NEC 690.64 (B) (2). 4. Plan view shows 21 panels. TEP model shows 18 panels. Please clarify. 5. Plan view shows panels hanging out over the edge of the roof. This is not an acceptable means of installation. 6. Elevation view shows panels straddling different elevations and hanging out over edges of various roof components. This is not an acceptable means of installation. |
| 06/20/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/20/2006 | TERRY STEVENS | NPPO | REVIEW | Passed | |
| 06/20/2006 | DANIEL RUSCH | BUILDING-RESIDENTIAL | REVIEW | Approved | |
| 06/20/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved |