Permit Number: T06CM03339
Parcel: 126070030

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03339
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
06/14/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03339 6/14/06

1. Heat pump is specified as 3-phase on Sheet M0.1, but is provided with single phase electrical power. Please clarify.
2. Provide fault calculations for New Panel A. This is listed as a new panel on the One Line Diagram and on the Power Plan, and as such it needs to be demonstrated that it is installed within its 10K rating.
06/14/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise ventilation calculations per the attached sheets.
06/15/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/15/2006 AKLAPPE1 WWM REVIEW Needs Review