Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03339
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/14/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/14/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM03339 6/14/06 1. Heat pump is specified as 3-phase on Sheet M0.1, but is provided with single phase electrical power. Please clarify. 2. Provide fault calculations for New Panel A. This is listed as a new panel on the One Line Diagram and on the Power Plan, and as such it needs to be demonstrated that it is installed within its 10K rating. |
06/14/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise ventilation calculations per the attached sheets. |