Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM03339
Parcel: 126070030

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03339
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2006 PETER MCLAUGHLIN ZONING REVIEW Approved
06/06/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide justification for ventilating an art studio as an office.
2. Clarify the status of the heat pump: existing or new; what are the electrical requirements?
06/06/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03339 6/6/06

1. Clarify status of heat pump. Panel schedule designates it as existing, but from the remainder of the plans this appears to be a new unit.
2. Clarify power requirements of heat pump. Schedule on Sheet M0.1 specifies an MCA of 75A. Yet the HP is protected by a 60A breaker. This would not be a circuit of sufficient size if the MCA data were correct.
3. Provide electrical line diagram of service and all panels on service.
4. Provide service load calculations.
5. Show location of electrical service on scaled drawing.
6. Provide fault calculations for New Panel A.
06/06/2006 ROBERT SHERRY WATER REVIEW Approved
06/06/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE EXTERIOR WALL SECTION FOR REPLACEMENT OF STOREFRONT.
2) CLARIFY ADJACENT TENANT OCCUPANCY.
06/06/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/06/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The controlling code is the 2003 UPC with COT amendments, not the IPC.
2. Water pressure in excess of 80 PSI necessitates a pressure regulator. If Table 6-5 is to be used for sizing the water pipes, refer to the last sentence in Section 608.2, UPC 2003.
3. Coordinate the fixture tag numbers in detail C2/P1.1 with the fixture schedule.
4. What is the "approved manner" of anchoring the water heater support to the wall?
06/07/2006 DAVE MANN FIRE REVIEW Approved
06/14/2006 AKLAPPE1 WWM REVIEW Needs Review