Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T06CM03275
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide plumbing design to show how the existing plumbing is to be modified. |
| 08/22/2006 | JWILLIA5 | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 08/22/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY / DIMENSION APPROACH TO FRONT DOOR PER 404.2.3.4 - MANEUVERING CLEARANCE AT RECESSED DOORS ANSI A117.1 2003. 2) PROVIDE LANDING AT TOP AND BOTTOM PER 405.7 ANSI a117.1 2003. 3) EDGE PROTECTION COMPLYING WITH 405.9 OR CLARIFY COMPLIANCE WITH EXCEPTIONS. 4) PROVIDE DIMENSIONS WIDTH AND RUN FOR ALL RAMPS. 5) PROVIDE OCCUPANT LOAD FOR SHARED FACILITIES TO JUSTIFY FIXTURE COUNT. 6) DOOR SWINGS ARE NOT ALLOWED TO SWING INTO TURNING RADIUS FOR MULTI OCCUPANT RESTROOM FACILITIES. SEE WOMEN'S RESTROOM. 7) CLARIFY CLEARANCES FOR URINAL FOR ACCESSIBILITY. 8) CLARIFY DOOR CLEARANCES FOR ENTERING AND EXITING EACH RESTROOM. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/08/2006 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 09/08/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 09/08/2006 | DELMA ROBEY | REJECT SHELF | Completed |