Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM03275
Parcel: 124050520

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM03275
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2006 CINDY AGUILAR APPROVAL SHELF Completed
08/11/2006 CINDY AGUILAR OUT TO CUSTOMER Completed