Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM03275
Parcel: 124050520

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM03275
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03275 8/10/06

1. Panel A carries 141 A, which exceeds the 130A ampacity of the #1 conductor on Keynote 7 of the Existing Service Diagram.
2. The Panel A Schedule lists this panel as 200A. According to Keynote 5 this is a 125A panel. Please clarify.
3. Panel A carries 141 A, which exceeds the 125A ampacity of the panel according to Keynote 5 of the Existing Service Diagram.
4. Keynote 6 on the Existing Service Diagram, represents Panel K. Please add this to the diagram itself.
5. If the intent is to show Panel K on Keynote 7, or #1 conductor, which has ampacity of 130A, please note that this conductor is not protected by the 150A CB indicated in Panel Schedule AC.
6. Keynotes 5 and 12 are both inserted by the panel fed from the 100A fusible disconnect. Please clarify which panel this is.
7. Keynote 12 is inserted by the grounding electrode system for both services. This keynote represents a panel. Please clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2006 DELMA ROBEY OUT TO CUSTOMER Completed