Permit Number: T06CM03275
Parcel: 124050520

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM03275
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03275 8/9/06

1. On panel schedule, fill in electrical load for K-4.
2. On panel schedule, fill in electrical load for K-34.
3. On panel schedule, fill in electrical load for A-39.
4. Ckt A-2,4 shows what appears to be a conventional duplex receptacle on a 2-pole circuit. Please clarify.
5. Ckt K-31,37 shows what appears to be a conventional duplex receptacle on a 2-pole circuit. These are 2 separate and distince circuits on the panel schedule. Please clarify.
6. Ckt K-7,9 shows what appears to be a conventional duplex receptacle on a 2-pole circuit. Please clarify.
7. Provide electrical line diagram.
8. Provide panel load calculations. No panel and no phase shall be overloaded.
9. Provide service load calculations.