Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T06CM03275
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/09/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM03275 8/9/06 1. On panel schedule, fill in electrical load for K-4. 2. On panel schedule, fill in electrical load for K-34. 3. On panel schedule, fill in electrical load for A-39. 4. Ckt A-2,4 shows what appears to be a conventional duplex receptacle on a 2-pole circuit. Please clarify. 5. Ckt K-31,37 shows what appears to be a conventional duplex receptacle on a 2-pole circuit. These are 2 separate and distince circuits on the panel schedule. Please clarify. 6. Ckt K-7,9 shows what appears to be a conventional duplex receptacle on a 2-pole circuit. Please clarify. 7. Provide electrical line diagram. 8. Provide panel load calculations. No panel and no phase shall be overloaded. 9. Provide service load calculations. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/10/2006 | CINDY AGUILAR | APPROVAL SHELF | Completed |
08/10/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |