Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM03275
Parcel: 124050520

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM03275
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03275 8/9/06

1. On panel schedule, fill in electrical load for K-4.
2. On panel schedule, fill in electrical load for K-34.
3. On panel schedule, fill in electrical load for A-39.
4. Ckt A-2,4 shows what appears to be a conventional duplex receptacle on a 2-pole circuit. Please clarify.
5. Ckt K-31,37 shows what appears to be a conventional duplex receptacle on a 2-pole circuit. These are 2 separate and distince circuits on the panel schedule. Please clarify.
6. Ckt K-7,9 shows what appears to be a conventional duplex receptacle on a 2-pole circuit. Please clarify.
7. Provide electrical line diagram.
8. Provide panel load calculations. No panel and no phase shall be overloaded.
9. Provide service load calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2006 CINDY AGUILAR APPROVAL SHELF Completed
08/10/2006 CINDY AGUILAR OUT TO CUSTOMER Completed