Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03273
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/01/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
06/01/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/01/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The use of a simplex sump pump will require an appeal to the building official. Reference section 710.9, UPC 2003. 2. Provide backflow protection for the directly-connected coffee maker. Reference Section 602.3, UPC 2003. |
06/01/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/01/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
06/01/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
06/12/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/13/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/15/2006 | GBONILL1 | WWM | REVIEW | Needs Review |