Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM03187
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/01/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Please clarify if the 250 MCM Al conductor sizes for the Panel 101H feeder are typical. Fault calculations appear to be based on this sizing. 2. Please eliminate the #3 GNDs on the line side of the disconnecting switches. 3. Provide a location for the new transformer and new disconnect in Ste 103 & 102. 4. Please clarify whether Panel 103L is existing or new. Line diagram indicates existing. Panel schedule indicates new. 5. Applicant shall go to Pima County Addressing to obtain addresses for all new meters. Take such addresses to DSD Permit Clerks for data entry into the City permitting system. Addresses for all new meters as shown on the plans shall correspond to those in City/County database. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/07/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 09/07/2006 | SUE REEVES | REJECT SHELF | Completed |