Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03177
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/02/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 06/02/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide reference drawings to show that the rooftop units are adequately supported on the roof. 2. Show the sizes and routes for the condensate drains |
| 06/02/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water riser diagram. 2. Provide detail for the water heater, showing the drain, shut off valve, T&P relief, and the expansion tank. 3. Clarify the design of the shower basin. 4. Show how the temperature of the hot water to the lavatories are limited to 110 degrees Fahrenheit. 5. Provide specifications for the plumbing fixtures and the water heater. 6. Show the size, route, and termination for the T&P relief. |
| 06/02/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/02/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/07/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/07/2006 | AOLIVO1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/07/2006 | AOLIVO1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |