Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2006 JASON GREEN ENGINEERING REVIEW Approved
06/02/2006 HEATHER THRALL ZONING REVIEW Approved
06/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide reference drawings to show that the rooftop units are adequately supported on the roof.
2. Show the sizes and routes for the condensate drains
06/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water riser diagram.
2. Provide detail for the water heater, showing the drain, shut off valve, T&P relief, and the expansion tank.
3. Clarify the design of the shower basin.
4. Show how the temperature of the hot water to the lavatories are limited to 110 degrees Fahrenheit.
5. Provide specifications for the plumbing fixtures and the water heater.
6. Show the size, route, and termination for the T&P relief.
06/02/2006 ROBERT SHERRY WATER REVIEW Approved
06/02/2006 DAVE MANN FIRE REVIEW Approved
06/07/2006 GERRY KOZIOL WWM REVIEW Approved
06/07/2006 AOLIVO1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/07/2006 AOLIVO1 BUILDING-COMMERCIAL REVIEW Needs Review