Permit Number: T06CM03116
Parcel: 123070950

Address:
1945 E MABEL ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM03116
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2006 GERRY KOZIOL WWM REVIEW Denied NEED 8TH FLOOR WASTEWATER CREDIT REVIEW
07/19/2006 ADRIAN ALEGRIA BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM03116

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

Construction drawing guidelines are available from the residential desk of the Development Services Division.

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All model plans shall reference these codes.
All code references to the International Residential Code shall be changed from 2000 to 2003 with appropriate paragraph references.
Correct illegible overtyped statements:
All dimensions and notes shall be consistent on each plan or elevation.
Provide a note for: Underground facility tracer wires per DSD Memo, 10/24/2005.

ELEVATIONS:
1. Clarify compliance with unvented roof and attic design #7 with section A-A on sheet A2, where section shows typical insulation installation.

STRUCTURAL PLANS:
1. Completely detail all connections to the foundation and/or framing members:
· Post to slab
· Field welds require special inspections. If used, a special inspection request must be included with the permit application.
2. Show details for typical non-bearing interior wall conditions (floor and rafter/joist connections & gaps).
3. Specify and detail all over-framing connections for intersecting pitched roof assemblies. Provide a minimum opening of 22" by 30" for access and ventilation between over-framed assemblies (>30 S.F.), R807
4. Please provide correction for cross sections details reference on roof framing plan for S4 sheet.

OUTDOOR LIGHTING CODE

1. Full cut-off fixtures have no emittance above the nadir (no deco openings, semi-opaque panels or exposed lamps). Fixtures may be exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).
2. Show compliance with City of Tucson Outdoor Lighting Code; the unshielded limit for area E3 is 12,000 lumens per acre. Include all exterior fixtures on the property in the calculations. Provide further information for fixture W1 /W2 (enclosed top). Also, 60 watt fixtures produce 850 lumens unless shown differently. Furthermore, fixture F1 may be considered FCO if the installed lamp does not extend below the fixture shielding. Provide lamp data for all FCO fixtures. Review guidance: www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf


If you have any questions, please contact your assigned plan examiner: Adrian Alegria 791-5550 ext.#1186

Final Status

Task End Date Reviewer's Name Type of Review Description
07/21/2006 GERARDO BONILLA OUT TO CUSTOMER Completed