Permit Number: T06CM03099
Parcel: 13319195A

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM03099
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2006 MARTIN BROWN FIRE REVIEW Approved
05/25/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show that the components for the gas train for the emergency generator comply with the requirements of NFPA 37. Reference Section 616.1, International Fuel Gas Code 2003.
05/26/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
05/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM03099 5/26/06

1. Show available fault current, from utility not just the generator, at transfer switch.
2. Indicate number of poles for transfer switch. Verify compliance with NEC 250.30 for separately derived systems.
06/01/2006 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
06/01/2006 DROBEY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/01/2006 DELMA ROBEY OUT TO CUSTOMER Completed