Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T06CM03099
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/24/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/25/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show that the components for the gas train for the emergency generator comply with the requirements of NFPA 37. Reference Section 616.1, International Fuel Gas Code 2003. |
| 05/26/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/26/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM03099 5/26/06 1. Show available fault current, from utility not just the generator, at transfer switch. 2. Indicate number of poles for transfer switch. Verify compliance with NEC 250.30 for separately derived systems. |
| 06/01/2006 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/01/2006 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/01/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |