Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM03068
Parcel: 13322471B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03068
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Roof top maint. receptacles shall be GFCI protected. 2.Circuiting is not reflected at panel schedule for these roof top receptacles. 3.Circuit A-6 is described as a lighting at panel schedule but is different on sheet A-4(please clarify). 4.Indicate water heater location and correct panel schedule to match.5.Panel140B isfed by 100 amp conductors but is protected at 200 amps (please clarify). 6.Indicate emergency egress lighting.
06/15/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06CM03068 .. 7225 EAST BROADWAY BOULEVARD, SUITE #140 .. MGM PARTNERS LLC OFFICE .. FIRST TENANT A B-OCCUPANCY OFFICE IN A M-OCCUPANCY RETAIL SHELL SPACE .. DGL .. 1ST REVIEW COMMENTS .. 6/20/06 ..

TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.

S1. Provide site plan with properly annotated property lines, access to a public way, dimension building from two adjacent property lines and from adjacent buildings, also indicate Occupancy of tenant spaces within this Shell Building.
S2. Provide completed Code Review Checklist, as required by 1997 Uniform Administrative Code Section 302.1, including: General Building Summary and Allowable Area Calculation. See DSD website : www.tucsonaz.gov/dsd, for form.
S3. Verify/Revise the font size used on the drawings to a minimum of 1/8 inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
S4. Address accessibility show conformance to 2003 IBC Section 11 and ANSI A117.1-2003ed.
S5. Show accessibility at break room and reception counter.
S6. Provide location/s of equipment on roof by dimension from two adjacent walls and provide structural calculations to show the structure is capable of supporting the roof-mounted equipment.
S7. Provide addressing per Pima County Addressing Ordinance and IBC section 501.2 on the drawings.


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/03/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed
07/03/2006 SUE REEVES REJECT SHELF Completed