Permit Number: T06CM03031
Parcel: 12510003F

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM03031
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2006 ROBERT SHERRY WATER REVIEW Approved
08/09/2006 MARTIN BROWN FIRE REVIEW Denied Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply (flow data, available from Tucson Fire Department)
4. The design density and the area of operation.
NOTE: Verify .60 density stated on plans is correct.
08/10/2006 GERRY KOZIOL WWM REVIEW Approved
08/14/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/14/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Shell building, no impact fees until first tenant.
09/12/2006 TERRY STEVENS ZONING REVIEW Approved