Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/16/2006 | ROBERT SHERRY | WATER | REVIEW | Passed | |
10/16/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | Basement must have sprinklers per IFC 903.2.10.1. Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply. 4. The design density and the area of operation. |
10/27/2006 | VFLORES1 | ENGINEERING | REVIEW | Needs Review | |
10/27/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
10/27/2006 | VFLORES1 | ZONING | REVIEW | Needs Review | |
10/27/2006 | VFLORES1 | WWM | REVIEW | Needs Review |