Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T06CM03012
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2006 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 10/16/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | Basement must have sprinklers per IFC 903.2.10.1. Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply. 4. The design density and the area of operation. |
| 10/27/2006 | VFLORES1 | ENGINEERING | REVIEW | Needs Review | |
| 10/27/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 10/27/2006 | VFLORES1 | ZONING | REVIEW | Needs Review | |
| 10/27/2006 | VFLORES1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/27/2006 | VFLORES1 | OUT TO CUSTOMER | Completed |